> unless you're worried about the breaker box flipping, ruining at 90% of the fuse rating is reasonable (if it is a stable 'non-inductive' load).
A continuous load (usually) requires a breaker rated at 125% of the load, as calculated by the electrical load. A 90A continuous load on a normal 100A breaker is not okay, full stop. It doesn’t matter if that load is literally a giant resistor or is some real-world device.
> If someone has had 100A service installed with 100A breakers and it's not wired for at least 125A with #2, then they have been defrauded by their electrician and contracor.
In the infamous words of Wikipedia, citation needed. In standard US residential usage, a “200A service” is 200A for non-continuous loads and needs to be wired for 200 Amps. Same for 100A, etc. The only common exception I’ve heard of is “class 320” service, which is genuinely rated for 320A continuously, and that’ll have 400A wiring and perhaps a 400A main breaker or a pair of 200A breakers. The latter seems fairly common, since you can buy the hardware at Home Depot.
Great, I'm glad for this new information. So when I go out to look at my breaker box which is billed as 200A (or 400 which they will at least tell me is really 320) service and it has two 100A (or 200A) breakers for a house/garage full of loads, I just hope it doesn't burn down?
As a home owner how will I ever discover this in a non-catastrophic way? Will I put an ammeter clamp on at the breaker box with an alarm on it? Will I know the load of everything that is plugged into that service? The breaker won't blow, but the building will burn down... and it's not the fault of the electrician who installed it and code enforcement says it's fine?
As examples of non-continuous loads that are likely to be continuous for 8 hours or more: a double oven during Thanksgiving, halogen flood lamps at night, or an electric space heater during winter. Oops, you burned your house down for Christmas.
(edit) Discussing this with an electrician, he says that in fact the breaker will flip after extended/continuous load near the breaker limit. It would not be considered a hazard, because the home owner would experience the breaker flip each time before there was a problem. He also said that it's the difference between running at 75 vs 100% of rated current is about 15C of increased temp on the wires and also not a concern for copper.
Yeah, your breaker box that's billed as 200A and has a 200A main breaker and wiring rated at 200A is quite safe. The breaker is designed to trip after a certain amount of time depending on RMS current, and the wiring is supposed to be able to tolerate that with some safety margin.
Your 40A (or whatever) oven isn't a 40A continuous load even on Thanksgiving. It'll draw 40A (maybe) while heating up, but it'll use much less while maintaining temperature.
If you really want, you can probably melt your breaker box, though. You'll need some really nasty nonlinear loads. Off the top of my head, with standard single-phase service, you want lots of even harmonics so that you draw 200A from each phase but put more like 400A on the neutral. Since your breaker doesn't sense neutral current, you won't trip it. (I suspect you'll acutally fry your utility's transformer long before you melt your breaker box, though -- most utilities use a rather different formula for transformer sizing and can't actually supply your rated current for very long.)
> unless you're worried about the breaker box flipping, ruining at 90% of the fuse rating is reasonable (if it is a stable 'non-inductive' load).
A continuous load (usually) requires a breaker rated at 125% of the load, as calculated by the electrical load. A 90A continuous load on a normal 100A breaker is not okay, full stop. It doesn’t matter if that load is literally a giant resistor or is some real-world device.
> If someone has had 100A service installed with 100A breakers and it's not wired for at least 125A with #2, then they have been defrauded by their electrician and contracor.
In the infamous words of Wikipedia, citation needed. In standard US residential usage, a “200A service” is 200A for non-continuous loads and needs to be wired for 200 Amps. Same for 100A, etc. The only common exception I’ve heard of is “class 320” service, which is genuinely rated for 320A continuously, and that’ll have 400A wiring and perhaps a 400A main breaker or a pair of 200A breakers. The latter seems fairly common, since you can buy the hardware at Home Depot.